Data Sheet

acc. to IEC 60947-2 230 V AC
2.1 W
at Rated Operating Conditions per Pole 2.1 W
Power Loss
acc. to IEC/EN 60664-1 440 V Rated Insulation Voltage (U
i
)
Maximum (Incl. Tolerance) 253 V AC
Maximum (Incl. Tolerance) 72 V DC
Maximum 253 V AC
Maximum 72 V DC
Minimum 12 V AC
Minimum 12 V DC
Operational Voltage
50 Hz
60 Hz
Rated Frequency (f)
(230 / 400 V AC) 6 kA Rated Short-Circuit Capacity (I
cn
)
(133 V AC) 20 kA
(230 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (I
cu
)
(133 V AC) 15 kA Rated Service Short-Circuit Breaking Capacity (I
cs
)
3 Energy Limiting Class
III Overvoltage Category
3 Pollution Degree
4 kV
(6.2 kV @ sea level)
(5.0 kV @ 2000 m)
Rated Impulse Withstand Voltage (U
imp
)
50 / 60 Hz, 1 min: 2 kV Dielectric Test Voltage
Insulation Group II, RAL 7035 Housing Material
Insulation group II, black, sealable Actuator Type
Red ON / Green OFF Contact Position Indication
IP20 Degree of Protection
IP40 in enclosure with cover Remarks
20000 AC cycle Electrical Endurance
20000 cycle
Screw Terminals Terminal Type
Failsafe Bi-directional Cylinder-lift Terminal Screw Terminal Type
Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
Connecting Capacity
2.8 N·m Tightening Torque
Pozidriv 2 Recommended Screw Driver
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting on DIN Rail
Any Mounting Position
Operation -25 ... +55 °C
Storage -40 ... +70 °C
Ambient Air Temperature
25g / 2 shocks / 13 ms Resistance to Shock acc. to IEC 60068-2-27
5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In Resistance to Vibrations acc. to IEC 60068-2-6
28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Environmental Conditions
Following EU Directive 2002/95/EC August 18, 2005 and amendment RoHS Status
Environmental
2 S201-C10