100 Electrical installation
WARNING! Before using tools, make sure that the nut/screw is not cross-
threading. Cross-threading will damage the drive and cause danger.
Tighten the combi screw to a torque of 30 N·m.
Tighten the conductor(s) to 40 N·m for frame R8 or to 70 N·m for frame R9.
T1/U, T2/V and T3/W terminals
Remove the nut that attaches the connector to its busbar.
Put the conductor under the connector pressure plate and pretighten the
conductor.
Put the connector back to its busbar. Start the nut, and turn it at least two
rotations by hand.
WARNING! Before using tools, make sure that the nut/screw is not cross-
threading. Cross-threading will damage the drive and cause danger.
Tighten the nut to a torque of 30 N·m.
Tighten the conductor(s) to 40 N·m for frame R8 or to 70 N·m for frame R9.
Note for cable lug installation (frames R6 to R9): Detach the connector and
install a cable lug to the terminal post / busbar as follows:
Remove the combi screw that attaches the connector to its terminal post /
busbar, and pull the connector off.
Attach the cable lug to the conductor.
Put the cable lug onto the terminal post / busbar. Start the nut, and turn it at
least two rotations by hand.
WARNING! Before using tools, make sure that the nut/screw is not cross-
threading. Cross-threading will damage the drive and cause danger.
Tighten the nut to a torque of 30 N·m.
12. U
nits with option +D150: Connect the brake resistor cable conductors to the R+
and R- terminals.
13. If parallel cable
s are installed (frames R8 and R9), install the grounding shelves
for them. Repeat steps 8 to 12.
14. Reinstall the shroud on the power terminals.
15. Reinstall the side plates of the cable entry box.
16. Install the control cable grounding shelf in the cable entry box.