Maintenance 135
Replacing the auxiliary cooling fan of frames R4 and R5 (IP55 and
option +C135) and IP21 frame R5 types ACS880-01-xxxx-7
WARNING! Obey the safety instructions, page 14. Ignoring the instructions
can cause physical injury or death, or damage to the equipment.
1. Disconnect the drive from the power line. Lock the main disconnecting device and
ensure by measuring that there is no voltage.
2. Remove the front cover. See page 96.
3. Unplug the fan power supply wires.
4. Lift the fan up.
5. Install the new fan in reverse order. Make sure that the arrow in the fan points to
the direction marked on the drive frame.
3
4
5