Hardware Manual

Table Of Contents
Maintenance 141
Replacing the drive (IP21, UL Type 1, frames R1 to R9)
This section gives instructions for replacing the drive module without the cable entry
box. This allows you to leave the cables installed (except from disconnecting the
conductors).
Note for IP55 (UL Type 12) drives: It is not allowed to remove the cable entry box.
WARNING! Obey the safety instructions, page 14. Ignoring the instructions
can cause physical injury or death, or damage to the equipment.
1. Disconnect the drive from the power line. Lock the main disconnecting device and
ensure by measuring that there is no voltage.
2. Remove the front covers. See section Connection procedure for frames R1 to R3
on page 91 or Connection procedure for frames R4 and R5 on page 94.
3. For frames R6 to R9:
Remove the side plates of the cable entry box by loosening
the mounting screws.
4. Disconnect the power and control cables.
5. Undo the screw(s) that fasten drive module to the cable entry box.
6. Undo the two screws that fasten drive module to the wall from top.
7. Undo the two screws which attach the drive module and cable entry box to the
wall. Leave the lower wall mounting screws of the cable box in place.
8. Lift the drive off.
9. Install the new drive module in reverse order.