Hardware Manual

Table Of Contents
Safety instructions 15
Grounding
These instructions are intended for all who are responsible for the grounding of the
drive.
WARNING! Ignoring the following instructions can cause physical injury,
death, increased electromagnetic interference and equipment malfunction:
Ground the drive, motor and adjoining equipment to ensure personnel safety
in all circumstances, and to reduce electromagnetic emission and
interference.
Make sure that grounding conductors are adequately sized as required by
safety regulations.
In a multiple-drive installation, connect each drive separately to protective
earth (PE).
Where EMC emissions must be minimized, make a 360° high frequency
grounding of cable entries in order to suppress electromagnetic disturbances.
In addition, connect the cable shields to protective earth (PE) in order to meet
safety regulations.
Do not install d drive with EMC filter options +E200 or +E202 on an
ungrounded power system or a high-resistance-grounded (over 30 ohms)
power system. See page 89.
Note:
Power cable shields are suitable for equipment grounding conductors only
when adequately sized to meet safety regulations.
Standard EN 61800-5-1 (section 4.3.5.5.2.) requires that as the normal touch
current of the drive is higher than 3.5 mA AC or 10 mA DC, you must use a
fixed protective earth connection and
a cross-section of the protective earthing conductor of at least 10 mm
2
Cu
or 16 mm
2
Al,
or
automatic disconnection of the supply in case of discontinuity of the
protective earthing conductor,
or
a second protective earthing conductor of the same cross-sectional area
as the original protective earthing conductor.