Hardware Manual

Table Of Contents
Technical data 159
Ex motor, sine filter, low noise
Contact ABB for the deratings of these cases:
drive is used with an ABB motor for explosive atmospheres (Ex) and EX motor in
Parameter 95.15 Special HW settings is enabled
sine filter given in the selection table on page 222 is used and ABB sine filter in
Parameter 95.15 Special HW settings is enabled
Low noise optimization is selected in Parameter 97.09 Switching freq mode.
Drive type
ACS880-01-
Output ratings
EX motor (ABB Ex motors) ABB Sine filter
Nominal use Light-
duty
use
Heavy-
duty use
Nominal use Light-
duty
use
Heavy-
duty
use
I
N
P
N
I
Ld
I
Hd
I
N
P
N
I
Ld
I
Hd
AkWAAAkWAA
U
N
= 230 V
04A6-2 4.6 0.75 4.4 3.7 4.3 0.55 4.1 3.5
06A6-2 6.6 1.1 6.3 4.6 6.2 0.8 5.9 4.3
07A5-2 7.5 1.5 7.1 6.6 7.4 1.5 7.0 6.2
10A6-2 10.6 2.2 10.1 7.5 10.0 2.2 9.5 7.4
16A8-2 16.8 4.0 16.0 10.6 15.9 4.0 15.1 10.0
24A3-2 24.3 5.5 23.1 16.8 23.1 5.5 21.9 15.9
031A-2 31 7.5 29.3 24.3 30.5 7.5 29.0 23.1
046A-2 46 11.0 44 38 43.0 11.0 41 31
061A-2 61 15 58 45 58 15 55 41
075A-2 75 19 71 61 65 15 62 55
087A-2 87 22 83 72 77 18.5 73 62
115A-2 106 22 101 87 100 22 95 73
145A-2 134 30 127 105 126 30 120 95
170A-2 161 37 153 134 153 37 145 120
206A-2 195 45 185 161 186 45 177 145
274A-2 251 55 238 195 233 55 221 169
U
N
= 400 V
02A4-3 2.4 0.75 2.3 1.80 2.3 0.55 2.2 1.7
03A3-3 3.3 1.1 3.1 2.4 3.1 0.75 2.9 2.3
04A0-3 4.0 1.5 3.8 3.3 3.8 1.1 3.6 3.1
05A6-3 5.6 2.2 5.3 4.0 5.3 1.5 5.0 3.8
07A2-3 8.0 3.0 7.6 5.6 7.2 2.2 6.8 5.3
09A4-3 10.0 4.0 9.5 8.0 9.2 3.0 8.7 7.2
12A6-3 12.9 5.5 12.0 10.0 12.1 4.0 11.5 9.2
017A-3 17 8 16 12.6 16 5.5 15 12
025A-3 25 11 24 17 23 7.5 22 16