Hardware Manual

Table Of Contents
164 Technical data
042A-7 40 30 38 33
049A-7 46 37 44 40
061A-7 49 45 47 46
084A-7 68 55 65 49
098A-7 83 75 79 68
119A-7 101 90 96 83
142A-7 101 90 96 84
174A-7 122 110 116 101
210A-7 138 132 131 122
271A-7 178 160 169 138
3AXD00000588487
U
N
Supply voltage range
I
N
Nominal output current (available continuously with no over-loading)
P
N
Typical motor power in no-overload use
I
Ld
Continuous rms output current allowing 10% overload for 1 minute every 5
minutes
I
Hd
Continuous rms output current allowing 50% overload for 1 minute every 5
minutes.
* Continuous rms output current allowing 30% overload for 1 minute every 5
minutes.
** Continuous rms output current allowing 25% overload for 1 minute every 5
minutes.
P
Hd
Typical motor power in heavy-duty use
Note 1: The ratings apply at an ambient temperature of 40 °C (104 °F).
Drive type
ACS880-01-
Output ratings with selection Low noise optimization of parameter
Parameter 97.09 Switching freq mode
Nominal use Light- duty use Heavy-duty use
I
N
P
N
I
Ld
I
Hd
AkWA A