Hardware Manual

Table Of Contents
168 Technical data
Fuses (IEC)
gG and aR fuses for protection against short-circuit in the input power cable or drive
are listed below. Either fuse type can be used for frames R1 to R6 if it operates
rapidly enough. The operating time depends on the supply network impedance and
the cross-sectional area and length of the supply cable. For frames R7 to R9 ultra-
rapid (aR) fuses must be used.
Note 1: See also Implementing thermal overload and short-circuit protection on page
75.
061A-7 120 500 44 42 40
084A-7 120 500 53 50 44
098A-7 120 500 68 65 53
119A-7 120 500 83 79 68
142A-7 120 500 83 79 72
174A-7 120 500 96 91 83
210A-7 120 500 101 96 83
271A-7 120 500 130 124 101
3AXD00000588487
f Output frequency
f
max
Maximum output frequency with High speed mode
U
N
Nominal voltage of the drive
I
N
Continuous rms output current. No overload capability at 40 °C (104 °F)
P
N
Typical motor power in no-overload use.
I
Ld
Continuous rms output current allowing 10% overload for 1 minute every 5
minutes
I
Hd
Continuous rms output current allowing 50% overload for 1 minute every 5
minutes
* Continuous rms output current allowing 40% overload for 1 minute every 5
minutes
** Continuous rms output current allowing 25% overload for 1 minute every 5
minutes
Drive
module
type
ACS880-
01-
Output ratings with selection High speed mode of parameter 95.15 Special
HW settings
120 Hz output frequency Maximum output frequency
f Nominal use Light-
duty
use
Heavy-
duty
use
f
max
Nominal use Light-
duty
use
Heavy-
duty
use
I
N
P
N
I
Ld
I
Hd
I
N
P
N
I
Ld
I
Hd
Hz A kW A A Hz A kW A A