Hardware Manual

Table Of Contents
Technical data 175
Quick guide for selecting between gG and aR fuses
The combinations (cable size, cable length, transformer size and fuse type) in this
table fulfil the minimum requirements for the proper operation of the fuse. Use this
table to select between gG and aR fuses or calculate the short-circuit current of the
installation as described under Calculating the short-circuit current of the installation
on page 178).
Drive type
ACS880-
01…
Cable type Supply transformer minimum apparent power S
N
(kVA)
Copper Aluminium Maximum cable length
with gG fuses
Maximum cable length
with aR fuses
mm
2
mm
2
10 m 50 m 100 m 10 m 100 m 200 m
U
N
= 230 V
04A6-2 3×1.5 - 1.1 1.1 - 1.1 1.2 -
06A6-2 3×1.5 - 2.2 2.4 - 1.1 1.2 -
07A5-2 3×1.5 - 3.3 4.3 - 1.1 1.2 -
10A6-2 3×1.5 - 3.3 4.3 - 1.5 1.8 -
16A8-2 3×6 - 5.5 5.8 - 1.8 1.8 -
24A3-2 3×6 - 9.7 11 - 3.3 3.5 -
031A-2 3×10 - 11 12 - 4.4 4.6 -
046A-2 3×16 3×35 14 15 - 7.7 8.2 -
061A-2 3×25 3×35 22 24 - 8.3 8.6 -
075A-2 3×35 3×50 28 29 - 11 11 -
087A-2 3×35 3×70 36 39 - 14 15 -
115A-2 3×50 3×70 48 52 - 19 21 -
145A-2 3×95 3×120 64 70 - 28 30 -
170A-2 3×120 3×150 93 104 - 36 39 -
206A-2 3×150 3×240 158 194 - 40 45 -
274A-2 2×(3×95) 2×(3×120) 198 229 - 57 62 -
U
N
= 400 V
02A4-3 3×1.5 - 0.82 0.82 0.82 3.1 3.4 5.0
03A3-3 3×1.5 - 1.9 1.9 2.0 3.1 3.4 5.0
04A0-3 3×1.5 - 1.9 1.9 2.0 3.1 3.4 5.0
05A6-3 3×1.5 - 3.8 4.0 4.4 3.1 3.4 5.0
07A2-3 3×1.5 - 3.8 4.0 4.4 3.1 3.4 5.0
09A4-3 3×1.5 - 5.8 6.2 8.4 3.1 3.4 5.0
12A6-3 3×1.5 - 5.8 6.2 8.4 3.1 3.4 5.0
017A-3 3×6 - 9.6 9.8 10 5.8 5.9 6.2
025A-3 3×6 - 12 12 13 5.8 5.9 6.2
032A-3 3×10 - 17 17 18 8.2 8.3 8.7
038A-3 3×10 - 19 20 21 8.2 8.3 8.7
045A-3 3×16 3×25 24 24 26 13 14 15
061A-3 3×25 3×25 39 39 42 18 19 20