192 Technical data
Electrical power network specification
Voltage (U
1
) ACS880-01-xxxx-2 drives: 208 … 240 V AC 3-phase
+10%…-15%. This is indicated in the type designation
label as typical input voltage level 3 230 V AC.
ACS880-01-xxxx-3
drives: 380 … 415 V AC 3-phase
+10%…-15%. This is indicated in the type designation
label as typical input voltage level 3 400 V AC.
ACS880-01-xxxx-5
drives: 380 … 500 V AC 3-phase
+10%…-15%. This is indicated in the type designation
label as typical input voltage levels 3 400/480/500
VAC.
ACS880-01-xxxx-7
drives: 525 … 690 V AC 3-phase
+10%…-15%. This is indicated in the type designation
label as typical input voltage levels 3 525/600/690
VAC.
Network type TN (grounded) and IT (ungrounded) systems.
Rated conditional short-circuit
current (IEC 61439-1)
65 kA when protected by fuses given in the fuse tables
Short-circuit current protection
(UL 508C,
CSA C22.2 No. 14-05)
US and Canada: The drive is suitable for use on a circuit
capable of delivering not more than 100 kA symmetrical
amperes (rms) at 600 V maximum when protected by
fuses given in the fuse table
Frequency 47 to 63 Hz, maximum rate of change 17%/s
Imbalance Max. ± 3% of nominal phase to phase input voltage
Fundamental power factor
(cos phi
1
)
0.98 (at nominal load)
Motor connection data
Motor types Asynchronous AC induction motors, permanent magnet
synchronous motors, AC induction servomotors and ABB
synchronous reluctance motors (SynRM motors) with
option +N7502
Voltage (U
2
) 0 to U
1
, 3-phase symmetrical, U
max
at the field weakening
point
Frequency 0…500 Hz
For drives with du/dt filter:
120 Hz
For drives with sine filter:
120 Hz
Current See section Ratings.
Switching frequency 2.7 kHz (typically)
~
~
~
~