Hardware Manual

Table Of Contents
Technical data 193
Maximum recommended motor
cable length
For ACS880-01-xxxx-2, ACS880-01-xxxx-3 and ACS880-
01-xxxx-5 frames R1 to R3 and for types ACS880-01-
07A3-7, ACS880-01-09A8-7, ACS880-01-14A2-7 and
ACS880-01-018A-7: 150 m (492 ft)
For ACS880-01-xxxx-2, ACS880-01-xxxx-3 and ACS880-
01-xxxx-5 frames R4 to R9 and for types from ACS880-01-
022A-7 to ACS880-01-271A-7: 300 m (984 ft).
Note: With motor cables longer than 150 m (492 ft) or
switching frequencies higher than default, the EMC
Directive requirements may not be fulfilled.
Control unit (ZCU-12) connection data
Power supply
(XPOW)
24 V (±10%) DC, 2 A
Supplied from the power unit of the drive, or from an
external power supply through connector XPOW (pitch
5 mm, wire size 2.5 mm
2
).
Relay outputs RO1…RO3
(XRO1 XRO3)
Connector pitch 5 mm, wire size 2.5 mm
2
250 V AC / 30 V DC, 2 A
Protected by varistors
+24 V output
(XD24:2 and XD24:4)
Connector pitch 5 mm, wire size 2.5 mm
2
Total load capacity of these outputs is 4.8 W (200 mA /
24 V) minus the power taken by DIO1 and DIO2.
Digital inputs DI1…DI6
(XDI:1 XDI:6)
Connector pitch 5 mm, wire size 2.5 mm
2
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Input type: NPN/PNP (DI1…DI5), NPN (DI6)
Hardware filtering: 0.04 ms, digital filtering up to 8 ms
DI6 (XDI:6) can alternatively be used as an input for PTC
sensors.
“0” > 4 kohm, “1” < 1.5 kohm
I
max
: 15 mA (for DI6 5 mA)
Start interlock input DIIL
(XD24:1)
Connector pitch 5 mm, wire size 2.5 mm
2
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Input type: NPN/PNP
Hardware filtering: 0.04 ms, digital filtering up to 8 ms