Hardware Manual

Table Of Contents
Mechanical installation 51
Frames R5 to R9 (IP21, UL Type 1)
1. See the dimensions in chapter Dimension drawings. Mark the locations for the
four or six mounting holes.
Note: The lowest holes/mounting screws are not necessarily needed. If you use
also them, you can replace the drive module without removing the cable entry box
from the wall.
2. Drill the mounting holes.
3. Start the screws or bolts into the mounting holes.
4. Position the drive module onto the screws on the wall.
5. Tighten the upper mounting screws in the wall securely.
6. Remove the front cover.
7. Attach the cable entry box to the drive frame. For instructions, see the assembly
drawing in the cable entry box. A view of frame R8 is shown below.
8. Tighten the lower mounting screws in the wall securely.