Mechanical installation 53
Frames R1 to R9 (IP55, UL Type 12)
Note: Do not open or remove the cable entry box for easier installation. The gaskets
do not fulfill the degree of protection if the box is opened.
1. See the dimensions in chapter Dimension drawings. Mark the locations for the
four or six mounting holes. The lowest holes are not necessarily needed.
2. Drill the mounting holes.
3. Start the upper screws or bolts into the mounting holes.
4. Position the drive onto the upper screws on the wall.
5. For UL Type 12 drives of frames R4 to R9:
Put the hood onto the upper screws.
6. Tighten the upper screws in the wall securely.
7. Start the lower screws or bolts into the mounting holes.
8. Tighten the lower screws in the wall securely.