68 Planning the electrical installation
Typical power cable sizes
The table below gives copper and aluminum cable types with concentric copper
shield for the drives with nominal current.
Cross-sectional area of the phase
conductors
S (mm
2
)
Minimum cross-sectional area of the
corresponding protective conductor
S
p
(mm
2
)
S <
16 S
16 < S <
35 16
35 < S S/2
Drive type
ACS880-
01-
Frame
size
IEC
1)
US
2)
Cu cable type Al cable
type
Cu cable type Al cable type
mm
2
mm
2
AWG/kcmil AWG/kcmil
U
N
= 230 V
04A6-2 R1 3×1.5 - 14 -
06A6-2 R1 3×1.5 - 14 -
07A5-2 R1 3×1.5 - 14 -
10A6-2 R1 3×1.5 - 14 -
16A8-2 R2 3×6 - 10 -
24A3-2 R2 3×6 - 10 -
031A-2 R3 3×10 - 8 -
046A-2 R4 3×16 3×35 6 -
061A-2 R4 3×25 3×35 4 -
075A-2 R5 3×35 3×50 3 -
087A-2 R5 3×35 3×70 3 -
115A-2 R6 3×50 3×70 1 -
145A-2 R6 3×95 3×120 2/0 -
170A-2 R7 3×120 3×150 3/0 -
206A-2 R7 3×150 3×240 250 MCM -
274A-2 R8 2 × (3×95)
3)
2 × (3×120) 2 × 3/0 -
U
N
= 400 V
02A4-3 R1 3×1.5 - 14 -
03A3-3 R1 3×1.5 - 14 -
04A0-3 R1 3×1.5 - 14 -
05A6-3 R1 3×1.5 - 14 -
07A2-3 R1 3×1.5 - 14 -
09A4-3 R1 3×1.5 - 14 -
12A6-3 R1 3×1.5 - 14 -
017A-3 R2 3×6 - 10 -
025A-3 R2 3×6 - 10 -