032A-3 R3 3×10 - 8 -
038A-3 R3 3×10 - 8 -
045A-3 R4 3×16 3×35 6 -
061A-3 R4 3×25 3×35 4 -
072A-3 R5 3×35 3×50 3 -
087A-3 R5 3×35 3×70 3 -
105A-3 R6 3×50 3×70 1 -
145A-3 R6 3×95 3×120 2/0 -
169A-3 R7 3×120 3×150 3/0 -
206A-3 R7 3×150 3×240 250 MCM -
246A-3 R8 2 × (3×70)
3)
2 × (3×95) 300 MCM -
293A-3 R8 2 × (3×95)
3)
2 × (3×120) 2 × 3/0 -
363A-3 R9 2 × (3×120) 2 × (3×185) 2 × 4/0 -
430A-3 R9 2 × (3×150) 2 × (3×240) 2 × 250 MCM -
U
N
= 500 V
02A1-5 R1 3×1.5 - 14
03A0-5 R1 3×1.5 - 14 -
03A4-5 R1 3×1.5 - 14 -
04A8-5 R1 3×1.5 - 14 -
05A2-5 R1 3×1.5 - 14 -
07A6-5 R1 3×1.5 - 14 -
11A0-5 R1 3×1.5 - 14 -
014A-5 R2 3×6 - 10 -
021A-5 R2 3×6 - 10 -
027A-5 R3 3×10 - 8 -
034A-5 R3 3×10 - 8 -
040A-5 R4 3×16 3×25 6 -
052A-5 R4 3×25 3×25 4 -
065A-5 R5 3×35 3×35 3 -
077A-5 R5 3×35 3×50 3 -
096A-5 R6 3×50 3×70 1 -
124A-5 R6 3×95 3×95 2/0 -
156A-5 R7 3×120 3×150 3/0 -
180A-5 R7 3×150 3×185 250 MCM -
240A-5 R8 2 × (3×70)
3)
2 × (3×95) 300 MCM -
260A-5 R8 2 × (3×70)
3)
2 × (3×95) 2 × 2/0 -
302A-5 R9 2 × (3×95) 2 × (3×120) 2 × 3/0 -
361A-5 R9 2 × (3×120) 2 × (3×185) 2 × 250 MCM -
Drive type
ACS880-
01-
Frame
size
IEC
1)
US
2)
Cu cable type Al cable
type
Cu cable type Al cable type
mm
2
mm
2
AWG/kcmil AWG/kcmil