Hardware Manual

Table Of Contents
Planning the electrical installation 77
03A3-3 R1 S 203 M/P-B/C 6 5 - -
04A0-3 R1 S 203 M/P-B/C 6 5 - -
05A6-3 R1 S 203 M/P-B/C 10 5 - -
07A2-3 R1 S 203 M/P-B/C 13 5 - -
09A4-3 R1 S 203 M/P-B/C 13 5 - -
12A6-3 R1 S 203 M/P-B/C 20 5 - -
017A-3 R2 S 203 M/P-B/C 25 5 - -
025A-3 R2 S 203 M/P-B/C 32 5 - -
032A-3 R3 S 203 M/P-B/C 50 5 - -
038A-3 R3 S 203 M/P-B/C 63 5 - -
045A-3 R4 S 803 S-B/C 63 10 - -
061A-3 R4 S 803 S-B/C 75 10 - -
072A-3 R5 S 803 S-B/C 125 10 1SDA067918R1 65
087A-3 R5 S 803 S-B/C 125 10 1SDA067918R1 65
105A-3 R6 - - 1SDA068555R1 65
145A-3 R6 - - 1SDA068555R1 65
169A-3 R7 - - 1SDA068555R1 65
206A-3 R7 - - 1SDA054141R1 65
246A-3 R8 - - 1SDA054365R1 65
293A-3 R8 - - 1SDA054420R1 65
363A-3 R9 - - 1SDA054420R1 65
430A-3 R9 - - 1SDA054420R1 65
U
N
= 500 V
02A1-5 R1 S 803 S-B/C 6 10 - -
03A0-5 R1 S 803 S-B/C 6 10 - -
03A4-5 R1 S 803 S-B/C 6 10 - -
04A8-5 R1 S 803 S-B/C 10 10 - -
05A2-5 R1 S 803 S-B/C 13 10 - -
07A6-5 R1 S 803 S-B/C 13 10 - -
11A0-5 R1 S 803 S-B/C 20 10 - -
014A-5 R2 S 803 S-B/C 25 10 - -
021A-5 R2 S 803 S-B/C 32 10 - -
027A-5 R3 S 803 S-B/C 50 10 - -
034A-5 R3 S 803 S-B/C 63 10 - -
040A-5 R4 S 803 S-B/C 63 10 - -
052A-5 R4 S 803 S-B/C 75 10 - -
065A-5 R5 S 803 S-B/C 125 10 1SDA067918R1 65
077A-5 R5 S 803 S-B/C 125 10 1SDA067918R1 65
096A-5 R6 - - 1SDA068555R1 65
Drive type
ACS880-01-
Frame
size
ABB miniature circuit breaker ABB moulded case circuit
breaker (Tmax)
Type kA
1)
Type kA
1)