78 Planning the electrical installation
1)
Maximum allowed rated conditional short-circuit current (IEC 61439-1) of the electrical power network
Protecting the motor and motor cable in short-circuits
The drive protects the motor cable and motor in a short-circuit situation when the
motor cable is sized according to the nominal current of the drive. No additional
protection devices are needed.
124A-5 R6 - - 1SDA068555R1 65
156A-5 R7 - - 1SDA068555R1 65
180A-5 R7 - - 1SDA054141R1 65
240A-5 R8 - - 1SDA054420R1 65
260A-5 R8 - - 1SDA054420R1 65
361A-5 R9 - - 1SDA054420R1 65
414A-5 R9 - - 1SDA054420R1 65
U
N
= 690 V
07A3-7 R5 S 803 S-B/C 13 4 1SDA067915R1 18
09A8-7 R5 S 803 S-B/C 20 4 1SDA067915R1 18
14A2-7 R5 S 803 S-B/C 25 4 1SDA067915R1 18
018A-7 R5 S 803 S-B/C 32 4 1SDA067916R1 18
022A-7 R5 S 803 S-B/C 50 4 1SDA067916R1 18
026A-7 R5 S 803 S-B/C 63 4 1SDA067916R1 18
035A-7 R5 S 803 S-B/C 63 4 1SDA067916R1 18
042A-7 R5 S 803 S-B/C 80 4 1SDA067917R1 18
1SDA054069R1 35
049A-7 R5 S 803 S-B/C 80 4 1SDA067917R1 18
1SDA054069R1 35
061A-7 R6 S 803 S-B/C 125 3 1SDA067918R1 20
1SDA054070R1 35
084A-7 R6 S 803 S-B/C 125 3 1SDA067918R1 20
1SDA054070R1 35
098A-7 R7 - - 1SDA068555R1 20
1SDA054071R1 35
119A-7 R7 - - 1SDA068555R1 20
1SDA054071R1 35
142A-7 R8 - - 1SDA068555R1 20
1SDA054071R1 35
174A-7 R8 - 1SDA054141R1 35
210A-7 R9 - 1SDA054365R1 35
271A-7 R9 - 1SDA054420R1 35
3AXD00000588487, 3AXD10000114581
Drive type
ACS880-01-
Frame
size
ABB miniature circuit breaker ABB moulded case circuit
breaker (Tmax)
Type kA
1)
Type kA
1)