Hardware Manual

Table Of Contents
88 Electrical installation
Motor and motor cable
Check the insulation of the motor and motor cable as follows:
1. Check that the motor cable is disconnected from the drive output terminals T1/U,
T2/V and T3/W.
2. Measure the insulation resistance between each phase conductor and then
between each phase conductor and the Protective Earth conductor using a
measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must
exceed 100 Mohm (reference value at 25 °C or 77 °F). For the insulation
resistance of other motors, please consult the manufacturer’s instructions. Note:
Moisture inside the motor casing will reduce the insulation resistance. If moisture
is suspected, dry the motor and repeat the measurement.
Brake resistor assembly
Check the insulation of the brake resistor assembly (if present) as follows:
1. Check that the resistor cable is connected to the resistor, and disconnected from
the drive output terminals R+ and R-.
2. At the drive end, connect the R+ and R- conductors of the resistor cable together.
Measure the insulation resistance between the combined conductors and the PE
conductor by using a measuring voltage of 1 kV DC. The insulation resistance
must be higher than 1 Mohm.
ohm
M
3~
U1
V1
W1
PE
ohm
ohm
R-
R+
PE