Datasheet

2CDC002137D0201 - 3
Miniature circuit breaker S 200 S
Tripping characteristics, internal resistance and power loss
Tripping characteristics
B characteristic C characteristic
2CDC022026F0210
2CDC022001F0210
Tripping characteristics acc. to IEC/EN 60898-1
Tripping
characteristic
Rated current Thermal release
1)
Electromagnetic release
2)
Currents Tripping time Range of instantaneous tripping Tripping time
conventional
non-tripping
current
I
1
conventional
tripping current
I
2
B 6 to 20 A 1.13 · I
n
1.45 · I
n
> 1 h
< 1 h
3 · I
n
5 · I
n
0.1 … 45 s
< 0.1 s
C 6 to 20 A 1.13 · I
n
1.45 · I
n
> 1 h
< 1 h
5 · I
n
10 · I
n
0.1 … 15 s
< 0.1 s
1)
The thermal releases are calibrated to a nominal reference ambient temperature; for B and C the reference value is 30 °C.
In the case of higher ambient temperatures, the current values fall by approx. 6 % for each 10 K temperature rise.
2)
The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz.
The thermal release operates independent of frequency.
Internal resistance and power loss
Tripping characteristic Rated current I
n
Internal resistance per pole
1)
Power loss per pole
1)
A m W
B, C 6 52.1 2.16
C 8 22.9 1.65
B, C 10 19.0 2.20
B, C 13 13.7 2.62
B, C 16 9.1 3.28
B, C 20 6.2 3.14
1)
Internal resistances and power loss are subject to application-specific and environment-specific conditions and are therefore to be considered as typical values.