Datasheet

6 - 2CDC002137D0201
Miniature circuit breaker S 200 S
Instructions for use
Connection and disconnection of different types of cables on the load side
Type of cables and cross sections
2CDC022027F0211
Connection of cables
2CDC022028F0211
Connection of one cable per opening
Rigid and flexible cables with end sleeves may be directly connected.
If flexible cables without end sleeves are to be connected, the terminal must be opened. Splicing of the wires must be
avoided.
The cable must be inserted into the terminal either as far as possible or in such a way that a sufficient connection is obvious.
The tightness of the connection must be checked.
Disconnection of cables
2CDC022029F0211
The cables may only be removed after operating the terminal’s opening mechanism.
If one cable is removed, the correct position of the remaining cable must be checked.
Processing instructions
The screwless terminal at the load side of the S 200 S is designed so that copper cables basically may be connected without
further preparation. If end sleeves are used as splicing protection for flexible cables, the compression of the end sleeves
must comply with the pull-out forces in accordance with standard IEC/EN 60898-1 table J.3.
Recommended tools for flexible cables with end sleeves
Crimp tool with trapezoid compression profile
Wire stripping length / size of end sleeves for all cables
Wire stripping length and end sleeve length 12 (+2) mm
Distribution boards with metal cover
The distance from a metallic cover to the “shoulder” of the miniature circuit breaker must be at least 6 mm on the load side
due to the arrangement of the easily accessible measurement point.