Cut Sheet

www.geindustrial.com BuyLog
Catalog
6-45
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Industrial Circuit Breakers
15-150A Circuit Breakers
Electronic Trip
Spectra
RMS
SE150 Line Circuit Breakers
SE150 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SED, SEH; 2-Pole, UL/CSA: 150A, 480 Vac Max., IEC 947-2: 160A, 415 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
UL 489 IC @480 Vac UL 489 IC @480 Vac
Adj. Inst. 18kA 25kA
Ampere
Trip Range Amps
Product Current Product Product Product Wire
Rating Low High Number Sensor Number Number Number Range
15 43 182 SRPE30A15
20 58 254 SRPE30A20
30 SEDA24AT0030
3
SEHA24AT0030
3
25 73 332 SRPE30A25
30 87 415 SRPE30A30
40 118 501 SRPE60A40
50 148 637 SRPE60A50 60 SEDA24AT0060
3
SEHA24AT0060
3
12-3/0 Cu
60 178 777 SRPE60A60
TCAL18 12-3/0 Al
70 206 863 SRPE100A70
80 236 999 SRPE100A80
100 SEDA24AT0100 SEHA24AT0100
90 267 1138 SRPE100A90
100 297 1280 SRPE100A100
110 328 1426 SRPE150A110
125 374 1640 SRPE150A125 150 SEDA24AT0150 SEHA24AT0150
150 450 1991 SRPE150A150
SE150 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SEL, SEP
2
; 2-Pole, UL/CSA: 150A, 480 Vac Max., IEC 947-2: 160A, 415 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
UL 489 IC @480 Vac UL 489 IC @480 Vac
Adj. Inst. 65kA 100kA
Ampere
Trip Range Amps
Product Current Product Product Product Wire
Rating Low High Number Sensor Number Number Number Range
15 43 182 SRPE30A15
20 58 254 SRPE30A20
30 SELA24AT0030
3
SEPA24AT0030
3
25 73 332 SRPE30A25
30 87 415 SRPE30A30
40 118 501 SRPE60A40
50 148 637 SRPE60A50 60 SELA24AT0060
3
SEPA24AT0060
3
12-3/0 Cu
60 178 777 SRPE60A60 TCAL18
70 206 863 SRPE100A70 12-3/0 Al
80 236 999 SRPE100A80
100 SELA24AT0100 SEPA24AT0100
90 267 1138 SRPE100A90
100 297 1280 SRPE100A100
110 328 1426 SRPE150A110
125 374 1640 SRPE150A125 150 SELA24AT0150 SEPA24AT0150
150 450 1991 SRPE150A150
2
SEL, SEP UL current limiting.
3
When used with 15-50A Rating Plug, UL listed for HID (high intensity discharge).
Note: All Spectra
breakers UL listed as HACR type.
All Spectra
breakers marked CE.
Product Number Structure
S EDA24AT0030
Frame Rating Interruption Continuous Voltage Trip Trip Sensor
Family (Amperes) Rating (480V) Load Rating Poles Rating Unit Function (Max Amps)
S = Spectra
E = 150 D = 18 kA A = Standard 2 = 2 poles 4 = 480V A = RMS1 T = LSI
1
0030
H = 25 kA 3 = 3 poles 6 = 600V 0060
L = 65 kA 0100
P = 100 kA 0150
1
Adjustable Instantaneous with Tracking Short Time (Long Time established via Interchangeable Rating Plugs).
Note: This information is provided for interpreting product numbers (it should not be used to build product numbers).