Installation Owner manual

64
UK
Key switch (see command)
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
073 Alarm behaviour for internal (C)
To change the alarm property for internal active (C):
1. On the control unit, enter:
073
2. The LCD display shows: 073: C = Internal
3. Via the keypad, select from the following items
and press:
0
C=Keypad
Only the control units are activated.
1
C=Internal
On alarm, the control units and the
internal alarm are activated.
2
C=Local
On alarm, the control units, the internal
alarm and the external siren are
activated.
3
C=Full
On alarm, the control units, the internal
signalling, the external sirens and the
exits are activated.
In a partitioned system
0
C=Keypad
Only the control units are activated.
1
C=Local
On alarm, the control units, the internal
alarm and external sirens are activated.
2
C=Full
Control unit + internal + external +
telephone dialler
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
075 Exit delay time internal C
To change the property of the exit delay time for internal
active C:
1. On the control unit, enter:
075
2. The LCD display shows: 075: E C=10
3. Via the keypad, select from the following items
and press:
1
Exit C=10
Exit delay time for internal active C is
10 seconds.
2
Exit C=20
Exit delay time for internal active C is
20 seconds.
3
Exit C=30
Exit delay time for internal active C is
30 seconds.
4
Exit C=45
Exit delay time for internal active C is
45 seconds.
5
Exit C=60
Exit delay time for internal active C is
60 seconds.
6
Exit C=120
Exit delay time for internal active C is
120 seconds.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer mode.