Technical Specifications

Acoustic Ceiling Products (ACP) – Classic X Section 09 53 36
February 26, 2013 SUSPENDED GRID SYSTEM
Digicon Information Inc. Page 2
B. ASTM E119-12a: Standard Test Methods for Fire Tests of Building Construction and
Materials.
C. ASTM E 580/580M-11b: Standard Practice for Installation of Ceiling Suspension Systems
for Acoustical Tile and Lay-in Panels in Areas Subject to Earthquake Ground Motions.
D. ASTM E1264-08e1: Standard Classification for Acoustical Ceiling Products.
E. CISCA (Ceilings & Interior Systems Contractors Association):
1. Ceiling Systems Handbook.
2. Acoustic Ceilings: Use and Practice.
F. EN 13501-1:2010: Fire classification of construction products and building elements -
Part 1: Classification using data from reaction to fire tests.
G. EN 13501-2:2007+A1:2009: Fire classification of construction products and building
elements - Part 2: Classification using data from fire resistance tests, excluding ventilation
services.
H. EN 13964:2004 + A1:2007: Suspended ceilings - Requirements and test methods.
I. USFDA (United States Food and Drug Administration).
1.4 SUBMITTALS FOR REVIEW
Do not request submittals if drawings sufficiently describe the products of this section or if proprietary
specifying techniques are used. Include a requirement for shop drawings only when special project
conditions exist or when reflected ceiling plans are not provided on the working drawings.
A. Section 01 33 00: Submission procedures.
B. Shop Drawings: Indicate grid layout and related dimensioning, junctions with other work,
interrelation of mechanical and electrical items related to system and [________].
C. Product Data: Provide data on grid system components and accessories.
Include the following paragraph for submission of physical samples for selection of finish, colour, surface
texture, etc.
D. Grid Samples: Submit [two] [____] samples each, [200] [____] mm ([8] [____] inches)
long, of grid system [top hanger,] [main runner,] [cross tee,] [wall molding,] and
[________].
1.5 SUBMITTALS FOR INFORMATION
The following submittals are informational; responsive action by the Consultant is not required.
A. Section 01 33 00: Submission procedures.
B. Manufacturer's Installation Instructions: Indicate special procedures, perimeter conditions
requiring special attention, and [________].