Operation Manual

66
3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Total capacity, TC
Interpolation Method:
x = 3.175kW
Sensible capacity, SC
Interpolation Method:
y = 2.107kW
40°C - 35°C
=
2.995kW - 3.295kW
40°C - 37°C 2.995kW - x
40°C - 35°C
=
1.917kW - 2.233kW
40°C - 37°C 1.917kW - y
Outdoor DB ° C
Indoor DB Indoor WB 35 37 40
° C ° C TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
23 15 3.295 2.233 xy2.995 1.917