Specifications

11
513-6 (Globe) / 1513-6 (Angle)
D
EEP WELL PUMP CONTROL
The ACV 513-6 pump control valve starts in an open position during
pump start-up, purging the deep well of air and debris to atmosphere.
Controlled closing of the valve, opens the mainline check valve, grad-
ually increasing line pressure. The valve reopens during shut-down
cycle to gradually decrease line pressure and prevent shock. Valve
and pump operations are interlocked by a limit switch assembly.
NOTE:
Energized to close valve.
Max W.P. standard to 10-125 psig
Optional:
125-250 psig
110-120 VAC, 50-60 Hz standard.
Optional:
specify voltage required.
Solenoid enclosure NEMA 1, 2, 3, 3S, 4, 4X
Manual operator standard
Limit switch enclosure general purpose
Standard with adjustable opening and closing speed.
QUICK SIZING: Valve size one to two sizes smaller than main line
Points to consider: – Refer to Engineering Data - Flow Capacity Chart
– The deep well pump valve must be sized so it relieves atmosphere
pump discharge pressure in excess of the normal system static pres-
sure. This is necessary to prevent premature opening of the main line
check valve. Refer to Engineering Data - Pressure Drop Chart. If flow
velocity exceeds 45 feet per second use next larger valve
– Pressure drop at required flow. Refer to Engineering Data - Pressure
Drop Chart
VALVE FUNCTION
Discharges deep well air and debris by being in an open position on pump
start-up.
– Closes at controlled rate (adjustable)
Eliminating surges when pumping into main line (works in conjunction with
controlled opening check valve in main line)
Opens at a controlled rate (adjustable) eliminating surges upon pump shut-off
– Valve and pump are electrically interlocked so pump power is shut-off when
valve is in near full open position (adjustable)
COMPONENTS
1. Main Valve 4. Adj. Opening Speed
2. Figure 51 Limit Switch 5. Adj. Closing Speed
3. 4-Way Solenoid 6. Y-Strainer
ACCESSORIES
Located as indicated X - Isolation Cocks
Included as marked
513-12 (Globe) / 1513-12 (Angle)
BOOSTER PUMP / DUAL CHAMBER / HYDRAULIC CHECK
Solenoid operated pump control for controlled opening and closing
on pump start-up and shut-down. Built on the dual chamber ACV
500 main valve. Equipped with hydraulic check feature to close valve
on pressure reversal. Valve and pump operations are interlocked by
a limit switch assembly.
NOTE:
Energized to open valve.
Max W.P. standard to 10-125 psig
Optional:
125-250 psig
110-120 VAC, 50-60 Hz standard.
Optional:
specify voltage required.
Solenoid enclosure NEMA 1, 2, 3, 3S, 4, 4X
Manual operator standard
Limit switch enclosure general purpose
Standard with adjustable opening and closing speed.
QUICK SIZING: Valve size same as line.
Points to consider: – Refer to Engineering Data - Flow Capacity Chart
– Pressure Drop at required flow
Refer to Engineering Data - Pressure Drop Chart
VALVE FUNCTION
Opens at a controlled rate on pump start-up (adjustable)
– Main valve upper chamber (A) connected to solenoid drain port
– Main valve lower chamber (B) connected to valve inlet (supply) port
– Closes at a controlled rate on pump shut-off (adjustable)
– Main valve upper chamber (A) connected to valve inlet (supply) port
– Main valve lower chamber (B) connected to solenoid drain port
– Valve and pump are electrically interlocked so that power is shut-off when
the valve is in near closed position (adjustable with limit switch)
– Check feature closes valve when discharge pressure exceeds
inlet pressure (power failure)
COMPONENTS
1. Main Valve 4. Adj. Opening Speed
2. Figure 51 Limit Switch 5. Adj. Closing Speed
3. 4-Way Solenoid 6. Check Valve
ACCESSORIES
Located as indicated X - Isolation Cocks Y - Y Strainer
Included as marked FC - Flo-Clean Strainer
PUMP CONTROL