Specifications

13
115-2 (Globe) / 1115-2 (Angle)
PRESSURE REDUCING / SUSTAINING
Automatically reduces a higher inlet pressure to a constant lower
outlet pressure regardless of changing flow rate and/or varying inlet
pressure. Equipped with a pressure sustaining control which prevents
the upstream pressure from dropping below a preset minimum.
NOTE:
Adjustment range:
Standard: 20-175 psig
Optional:
0-30 psig
100-300 psig
(stainless steel control)
Additional Combinations:
115-11 Reducing/Sustaining/Check
115-32 Reducing/Sustaining/Solenoid
QUICK SIZING:
Valve size one size smaller than line.
Points to consider:
– See Engineering Data - Pressure Reducing Sizing
Check maximum and minimum flow
Check pressure drop - pressure reducing valves or cavitation chart
If valve size required is smaller than line size, consider ACV 6115-2
Consult Watts ACV representative/factory
VALVE FUNCTION
Reduce higher inlet pressure to constant lower outlet pressure (adjustable)
Prevents upstream pressure from dropping below a preset minimum (adjustable)
COMPONENTS
1
. Main Valve
2. Pressure Reducing Control
3. Sustaining Control
4. Adj. Opening Speed (3” and Smaller)
5. Fixed Orifice
ACCESSORIES X - Isolation Cocks
Located as indicated Y - Y-Strainer
Included as marked L - Limit Switch
FC - Flo-Clean Strainer
P - Position Indicator
ACS - Adjustable Closing Speed
PRESSURE REDUCING
Flow Direction Shown: Under the Seat
Optional ‘R’ Flow Over the Seat: 115-2R/1115-12R
115-3 (Globe) / 1115-3 (Angle)
PRESSURE REDUCING / CHECK
Automatically reduces a higher inlet pressure to a constant lower
outlet pressure regardless of changing flow rate and/or varying inlet
pressure. Equipped with a hydraulic check feature to prevent reverse
flow on pressure reversal.
NOTE:
Adjustment range:
Standard: 20-175 psig
Optional:
0-30 psig
100-300 psig
(stainless steel control)
QUICK SIZING:
Valve size one size smaller than line.
Points to consider:
– See Engineering Data - Pressure Reducing Sizing
Check maximum and minimum flow
Check pressure drop - pressure reducing valves or cavitation chart
If valve size required is smaller than line size, consider ACV 6115-3
Consult Watts ACV representative/factory
VALVE FUNCTION
Reduces higher inlet pressure to constant lower outlet pressure (adjustable)
Close when outlet/downstream pressure exceeds inlet/upstream pressure
COMPONENTS
1. Main Valve
2. Pressure Reducing Control
3. Check Valve
4. Adj. Opening Speed (3” and Smaller)
5. Fixed Orifice
ACCESSORIES
Located as indicated X - Isolation Cocks FC - Flo-Clean Strainer
Included as marked Y - Y-Strainer P - Position Indicator
L - Limit Switch
ACS - Adjustable Closing Speed
Flow Direction Shown: Under the Seat
Optional ‘R’ Flow Over the Seat: 115-3R/1115-3R