Specifications

14
115-4 (Globe) / 1115-4 (Angle)
PRESSURE REDUCING / SOLENOID ON-OFF
Automatically reduces a higher inlet pressure to a constant lower
outlet pressure regardless of changing flow rate and/or varying inlet
pressure. Equipped with a solenoid override feature allowing for
electrical on-off operation of the valve.
NOTE:
Adjustment range:
Standard: 20-175 psig
Optional:
0-30 psig
100-300 psig (uses stainless
steel control)
Solenoid max W.P.:
At time of order, advise factory actual
system working pressure for correct
solenoid selection.
(consult factory if over 150 psig).
Enclosure NEMA 1, 2, 3, 3S, 4, 4X
Optional:
explosion proof NEMA 3, 3S, 4, 4X, 6, 6P, 7, 9
Additional combinations:
115-5 Pressure Reducing/Solenoid/Check
SPECIFY:
Energized to open or energized to close main valve.
QUICK SIZING: Valve size one size smaller than line.
Points to consider:
– See Engineering Data - Pressure Reducing Sizing
Check maximum and minimum flow
Check pressure drop - pressure reducing valves or cavitation chart
If valve size required is smaller than line size, consider ACV 6115-4
Consult Watts ACV representative/factory
PRESSURE REDUCING
Flow Direction Shown: Under the Seat
Optional ‘R’ Flow Over the Seat: 115-4R/1115-4R
115-7 (Globe) / 1115-7 (Angle)
PRESSURE REDUCING / SURGE
Automatically reduces a higher inlet pressure to a constant lower
outlet pressure regardless of changing flow rate and/or varying inlet
pressure. Should flow rate decrease rapidly a pressure controlled
surge pilot closes the valve to prevent downstream pressure buildup.
Excellent in dead-end systems and/or systems using high demand,
on-off equipment.
NOTE:
Adjustment range reducing/surge:
Standard: 20-175 psig
Optional:
0-30 psig
100-300 psig
(stainless steel control)
Additional combinations:
115-43 Reducing/Surge/Sustaining
115-50 Reducing/Surge/Check
QUICK SIZING:
Valve size one size smaller than line.
Points to consider:
– See Engineering Data - Pressure Reducing Sizing
Check maximum and minimum flow
Check pressure drop - pressure reducing valves or cavitation chart
If valve size required is smaller than line size, consider ACV 6115-7
Consult Watts ACV representative/factory
VALVE FUNCTION
Reduces higher inlet pressure to constant lower, outlet pressure (adjustable)
Closes quickly when outlet exceeds set point of surge control (adjustable)
COMPONENTS
1. Main Valve
2. Pressure Reducing Control
3. Surge Control
4. Fixed Orifice
5. Adj. Opening Speed (3” and Smaller)
ACCESSORIES
Located as indicated X - Isolation Cocks
Included as marked Y - Y-Strainer
L - Limit Switch
FC - Flo-Clean Strainer
P - Position Indicator
ACS - Adjustable Closing Speed
Flow Direction Shown: Under the Seat
Optional ‘R’ Flow Over the Seat: 115-7R/1115-7R
VALVE FUNCTION
Reduce higher inlet pressure to constant lower outlet pressure (adjustable)
Electrical on/off override of reducing function
C
OMPONENTS
1. Main Valve
2. Pressure Reducing Control
3. 2-Way Solenoid
4. Fixed Orifice
5. Adj. Opening Speed (3” and Smaller)
ACCESSORIES X - Isolation Cocks
Located as indicated Y - Y-Strainer
Included as marked L - Limit Switch
FC - Flo-Clean Strainer
P - Position Indicator
ACS - Adjustable Closing Speed