Specifications

21
FIRE PROTECTION VALVES
100D-A Globe
DELUGE VALVE/PNEUMATIC - HYDRAULIC - UL LISTED
The Watts ACV 100D-A deluge valve meets all requirements
for UL Listed, fire protection service. Valve opens on
demand to provide water flow to the fire protection sprinkler
s
ystem. Pilot system can be hydraulically, pneumatically or
manually operated. Opening of valve is by loss of control
pressure or by manual opening.
V
ALVE FUNCTION
– Valve closes when air / hydraulic pressure is applied to the cover of control 2
– Valve opens when air / hydraulic pressure is relieved from the cover of control 2
– Manual by-pass allows manual opening of the valve
COMPONENTS
1. Main Valve – Deluge 4. Ball Valve
2. 100M (Pneumatic/Hydraulic Control) FC – Flo-Clean Strainer
3. Fixed Orifice Restriction
Valve sizes approved by UNDERWRITER’S LABORATORIES:
4", 6", 8", 10"
Available in Cast Iron 125# and Cast Steel 150#,
with either Copper tubing and Brass fittings, or
Stainless Steel tubing and fittings.
UL LISTED
6M88
100D-B Globe
DELUGE VALVE/ELECTRONICALLY ACTUATED (SOLENOID)
– UL LISTED
The Watts ACV 100D-B deluge valve meets all requirements
for
UL Listed, fire protection service. Valve opens on demand to
provide water flow to the fire protection sprinkler system.
Pilot system can be hydraulically, pneumatically or manually
operated. Opening of valve is by electrical signal or by
manual opening.
VALVE FUNCTION
– Valve opens when solenoid is energized
– Valve closes when solenoid is de-energized
– Manual by-pass provides manual override of controls
COMPONENTS
1. Main Valve – Deluge 4. Ball Valve
2. 100M (Pneumatic/Hydraulic Control) 5. 3-Way Solenoid
3. Fixed Orifice Restriction 6. FC – Flo-Clean Strainer
Valve sizes approved by UNDERWRITER’S LABORATORIES:
4", 6", 8", 10"
Available in Cast Iron 125# and Cast Steel 150#,
with either Copper tubing and Brass fittings, or
Stainless Steel tubing and fittings.
UL LISTED
6M88