113-6 (Globe) / 1113-6 (Angle)
SOLENOID ON/OFF (OPEN/CLOSE) WITH HIGH
CAPACITY CONTROLS
A 3-way solenoid and auxiliary 3-port accelerator cause the main
valve to open fully or close drip-tight depending upon the actuation
position of the solenoid, energized to open/energized to close. The
high capacity accelerator assures quick valve response to the sole-
noid signal regardless of the main valve size. The valve may be
remotely operated by timers, relays, probes or any triggering device
to the solenoid.
NOTE:
Energized to open valve.
Optional:
energized to close valve.
At time of order, advise factory actual system
working pressure for correct solenoid selection.
110-120 VAC, 50-60 Hz standard
Optional:
specify voltage required.
Enclosure General Purpose (NEMA 1, 2, 3, 3S, 4, 4X)
Optional:
explosion proof (NEMA 3, 3S, 4, 4X, 6, 6P, 7, 9)
Manual operator standard
Standard with adjustable opening and closing speed.
QUICK SIZING: Valve size same as line or one size smaller.
Points to consider:
– Refer to Engineering Data - Flow Capacity Chart
– Pressure drop at required flow
Refer to Engineering Data - Pressure Drop Chart
– If valve size required is smaller than line size, consider ACV 6113-12
Consult Watts ACV representative/factory
SOLENOID CONTROL
113-12 (Globe) / 1113-12 (Angle)
SOLENOID ON/OFF (OPEN/CLOSE) Sizes 1
1
/4" - 4"
Operated by a 3-way solenoid, the main valve opens fully or closes
drip-tight depending upon the actuation position of the solenoid,
energized to open/energized to close. The valve may be remotely
operated by timers, relays, probes or any triggered device to
the solenoid.
NOTE:
Energized to open valve.
Optional:
energized to close valve.
At time of order, advise factory actual system working pressure
for correct solenoid selection.
110-120 VAC, 50-60 Hz standard
Optional:
specify voltage required.
Enclosure General Purpose (NEMA 1, 2, 3, 3S, 4, 4X)
Optional:
explosion proof (NEMA 3, 3S, 4, 4X, 6, 6P, 7, 9)
Manual operator standard
Optional:
Opening and/or closing speed.
QUICK SIZING: Valve size same as line or one size smaller.
Points to consider:
– Refer to Engineering Data - Flow Capacity Chart
– Pressure drop at required flow
Refer to Engineering Data - Pressure Drop Chart
– If valve size required is smaller than line size, consider ACV 6113-12
Consult Watts ACV representative/factory
V
ALVE FUNCTION
–Electrically operated on/off (open/close) control valve
COMPONENTS
1
. Main Valve
2. 3-Way Solenoid
3. Flo-Clean Strainer
ACCESSORIES X - Isolation Cocks
Located as indicated Y -Y - Strainer (Eliminates Flo-Clean)
Included as marked ACS - Adj. Closing Speed
ADS - Adj. Opening Speed
CLOSES VALVE
OPENS VALVE
Flow Direction Shown: Under the Seat
O
ptional ‘R’ Flow Over the Seat: 113-12R/1113-12R
Flow Direction Shown: Under the Seat
Optional ‘R’ Flow Over the Seat: 113-6R/1113-6R
VALVE FUNCTION
–Electrically operated on/off (open/close) control valve
–High capacity control for fast response
COMPONENTS
1. Main Valve 4. Adj. Closing Speed
2. 3-Way Solenoid 5. Adj. Opening Speed
3. Flo-Clean Strainer 6. Accelerator Control
ACCESSORIES X - Isolation Cocks
Located as indicated Y -Y - Strainer (Eliminates Flo-Clean)
Included as marked L - Limit Switch
P - Position Indicator