Specifications

9
PUMP CONTROL
113-46 (Globe) / 1113-46 (Angle)
B
OOSTER PUMP CONTROL (Valves 4" and smaller)
Solenoid operated pump control for controlled opening and closing
on pump start-up and shut-down. Equipped with hydraulic check
feature to close valve on pressure reversal and shut-off pump
in event of pump failure. Valve and pump operations are interlocked
by a limit switch assembly.
NOTE:
Energized to open valve.
At time of order, advise factory actual system
working pressure for correct solenoid selection.
110-120 VAC, 50-60 Hz standard
Optional:
specify voltage required.
Solenoid enclosure NEMA 1, 2, 3, 3S, 4, 4X
Manual operator standard
Limit switch enclosure general purpose
Standard with adjustable opening and closing speed.
Additional combinations:
413-46 Pump Control/Lift-Check
QUICK SIZING: Valve size same as line.
Points to consider:
– Refer to Engineering Data - Flow Capacity Chart
– Pressure drop at required flow
Refer to Engineering Data - Pressure Drop Chart
VALVE FUNCTION
– Opens at a controlled rate on pump start-up (adjustable)
Closes at a controlled rate on pump shut-off (adjustable)
– Valve and pump are electrically interlocked so that power is shut-off when
t
he valve is in near closed position
COMPONENTS
1. Main Valve 5. Adj. Closing Speed
2. 3-Way Solenoid 6. Check Valve
3. Fig. 51 Limit Switch FC – Flow CLean Strainer
4. Adj. Opening Speed
ACCESSORIES
Located as indicated X - Isolation Cocks
Included as marked Y -Y - Strainer
Flow Direction Shown: Under the Seat
Optional ‘R’ Flow Over the Seat: 113-46R/1113-46R
CLOSES VALVE
OPENS VALVE
113-21 (Globe) / 1113-21 (Angle)
BOOSTER PUMP CONTROL (Valves 6" and larger)
Solenoid operated pump control for controlled opening and closing
on pump start-up and shut-down. Equipped with hydraulic check
feature to close valve on pressure reversal. Valve and pump
operations are interlocked by a limit switch assembly.
NOTE:
Energized to open valve.
At time of order, advise factory actual system
working pressure for correct solenoid selection.
110-120 VAC, 50-60 Hz standard
Optional:
specify voltage required.
Solenoid enclosure NEMA 1, 2, 3, 3S, 4, 4X
Manual operator standard
Limit switch enclosure general purpose
Standard with adjustable opening and closing speed.
QUICK SIZING: Valve size same as line.
Points to consider:
– Refer to Engineering Data - Flow Capacity Chart
– Pressure drop at required flow
Refer to Engineering Data - Pressure Drop Chart
VALVE FUNCTION
– Opens at a controlled rate on pump start-up (adjustable)
– Closes at a controlled rate on pump shut-off (adjustable)
– Valve and pump are electrically interlocked so that power is shut-off when
the valve is in near closed position
Check feature closes valve when discharge pressure exceeds inlet pressure
(power failure or pump failure)
COMPONENTS
1. Main Valve 5. Check Valve
2. Accelerator Control 6. Adj. Closing Speed
3. Figure 51 Limit Switch 7. Adj. Opening Speed
4. 3-Way Solenoid
ACCESSORIES
Located as indicated X - Isolation Cocks Y -Y - Strainer
Included as marked FC - Flo-Cleaner Strainer