Multi channel:
All channels taking measurement from port 160 is sub port 2.
[CHANNEL_2]
NAME=Pressure
MODE=1
PORT=160
SUBPORT=2
CALC=*20
ALARMLOW = 6 alarm is set under 6 bar
ALARMHIGH=12
ALARMHIGHLIMIT=20 alarm is set between 12 and 20 bar.
ALARM=1 execute alarm_1 if true
[CHANNEL_3]
NAME=Pressure
MODE=1
PORT=160
SUBPORT=2
CALC=*20
ALARMHIGH=23
ALARMHIGHLIMIT=26 alarm is set between 23 and 26 bar.
ALARM=2 execute alarm_2 if true
[CHANNEL_4]
NAME=Pressure
MODE=1
PORT=160
SUBPORT=2
CALC=*20
ALARMHIGH=30 alarm is set above 30 bar.
ALARM=3 execute alarm_3 if true
Measurements via Ethernet:
[CHANNEL_4]
NAME=Pressure
MODE=1
PORT=160
SUBPORT=2
CALC=*20
ALARMHIGH=30 alarm is set above 30 bar.
UPDATETIMER=60 send every 60 seconds the measured value
REMOTE=192.168.1.12 address of receiving station. measurepoint.your site.com
is also allowed