Network Router User Manual

3. Network Integration and Management
3.1. Manual Mode Example
Conguring in Manual Mode
is section contains step-by-step instructions on conguring two GRouter devices to tunnel
709.1 packets over IP between each other. is will create an IP backbone for a 709.1 network.
Using the web conguration pages, set up IP addresses, subnet masks, and IP gateway
addresses for the two routers. Connect the routers to the same IP network. Using a PC
attached to the network, verify that the routers can be pinged. Consult with the network
administrator to procure the IP address, subnet mask, and gateway address, if not already
known.
Set both routers to manual mode. is is done on the Router Setup Page.
Add each router’s IP address and communications port number (the default port is 1628) into
the other routers channel list. Set the addressing type to unicast or multicast in the channel
details menu. is is done on the Channel List Page.
Once steps 1–3 have been completed, the routers will be able to communicate with each other
over the IP network. is can be veried by pressing the service pin on one of the routers and
checking the Diagnostics Page on the other router for packets received. e elds Data
Packets Received” and “IP Packets Received” should increase with each service pin.
For the routers to tunnel trac, the 709.1 interfaces must be set up. is can be done on the
709 Setup Page or with a network management tool such as LonMaker. Refer to the
management tool's documentation on commissioning routers. For example, the GRouter can
be commissioned using the Router icon within LonMaker.
3.2. Normal Mode With i.LON Conguration Server Example
is section contains step-by-step instructions on conguring the GRouter device with an i.LON
Conguration Server .
Using the web conguration pages, set up IP address(es), subnet mask(s), and IP gateway
address(es) for the router(s). Connect the router(s) to the same IP network as the PC running
the conguration server. Using a PC attached to the network, verify that the routers can be
pinged. Consult with the network administrator to procure the IP address, subnet mask, and
gateway address, if not already known.
Set the router(s) to normal mode. Set the conguration server address to the address of the
computer that is running the i.LON Conguration Tool. Set the conguration server port to
that used by the i.LON conguration server. e default is 1629. Set the compatibility type to
i.LON Conguration Server. Register the device with the conguration server by clicking on
the Register With Cong Server button. is is done on the Router Setup Page.
Go to the i.LON conguration server window and drag the GRouter device from the orphans
list to the desired channel. e router(s) should be added to the same channel. Aer a few
seconds, the router devices should turn green.
-61-