Based Data Acquisition and Control System User's Manual

Installation Guideline
2.1 General
Environmental Specifications
The following table lists the environmental specifications that general ly
apply to the ADAM-5000 system (System kernel and I/O modules).
Specification
Rating
Storage
temperature
-13
to
185°F
(-25
to
85°C)
Ambient
operating
temperature
14
to
158°F
(-10
to
70°C)
Ambient
humidity*
5
to
95%,
non-condensing
Atmosphere
No
corrosive
gases
* Equipment will operate below 30% humidity. However, static
electricity problems occur much more frequently at lower humidity
levels. Make sure you take adequate precautions before you touch
the equipment. Consider using ground straps, antistatic floor
cover- ings, etc. if you use the equipment in low humidity
environments.
Power Requirements
Although the ADAM-5000 systems are designed for standard
industrial unregulated 24 V
DC
power supply, they accept any power unit
that supplies within the range of +10 to +30V
DC
. The power supply
ripple must be limited to 100 mV peak-to-peak, and the immediate ripple
voltage should be maintained between +10 and +30 V
DC
.
Diagnostic Indicators
Diagnostic indicators are located on the front panel of the ADAM
system. They show both normal operation and system status in your
remote I/O system. The indicators are:
System status (PWR, RUN)
Communication status (TX, RX)
I/O module status
2-2 ADAM-5000