Product data

PRODUCT DATASHEET
SM HGFHHF 1-A.1 GB 2-3
2.3 HGF018 / HHF018 // YGF018
Model Indoor Unit
HGF018/HHF018
Model Outdoor Unit
YGF018
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity (4) kW 5.30 5.70
Power input (4) kW 1.64 1.67
EER (Cooling) or COP(Heating) (4) W/W 3.23 3.41
Energy efficiency class A B
V 220-240
Ph 1
Power supply
Hz 50
Rated current A 7.8 7.9
Power factor 0.92 0.92
Prated (IDU+ODU) W 2550
Circuit breaker rating A 25A
Fan type & quantity Crossflow x 1
Cooling SH/H/M/L RPM 1350/1200/1050/900
Fan speeds
Heating SH/H/M/L RPM 1350/1200/1050/900
Air flow (1) SH/H/M/L m3/hr 850/780/650/550
External static pressure Min Pa 0
Sound power level (2) SH/H/M/L dB(A) 58/55/52/48
Sound pressure level(3) SH/H/M/L dB(A) 48/45/42/38
Moisture removal l/hr 3.0
Condensate drain tube I.D mm 16
Dimensions WxHxD mm 940x298x200
Net Weight kg 13
Package dimensions WxHxD mm 1010x380x285
INDOOR
Packaged weight kg 17
Refrigerant control Capillary
Compressor type, model Rotary, HITACHI - ASH210SV-C8LU
Fan type & quantity Propeller(direct) x 1
Fan speeds H RPM 860
Air flow H m3/hr 2790
Sound power level H dB(A) 64
Sound pressure level(3) H dB(A) 54
Dimensions WxHxD mm 913x680x378
Net Weight kg 46
Package dimensions WxHxD mm 994x725x428
Packaged weight kg 50
Refrigerant type R410A
Standard charge kg(4m) 1.5
Additional charge g/m 30g/m(4m<L<25m)
Liquid line In.(mm) 1/4"(6.35)
Suction line In.(mm) 1/2"(12.7)
Max.tubing length m. Max. 25
OUTDOOR
Connections
between units
Max.height difference m. Max. 10
Operation control type Remote control
(1)Airflow in ducted units; at nominal external static pressure.
(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).