F When tightening the flare nut with torque wrench, ensure the direction for tight-
ening follows the arrows on the wrench.
Pipe Size Torque
Liquid Side(φ6 or 1/4 inch) 1.8 kg.m
Liquid Side (φ10 or 3/8 inch) 3.5 kg.m
Liquid Side(φ12 or 1/2 inch) 5.5 kg.m
Gas Side (φ10 or 3/8 inch) 3.5 kg.m
Gas Side(φ12 or 1/2 inch) 5.5 kg.m
Gas Side(φ16 or 5/8 inch) 7.5 kg.m
Gas Side(φ19 or 3/4 inch) 10.0 kg.m
l Connecting the cable to the outdoor unit as shown in OPERATING AND
INSTALLATION INSTRUCTIONS MANUAL.