Model No:
AC-S10CK_S10HK
Version 1.0
Indoor unit
Pipe length is
15 meters Max
Outdoor unit
e
l
e
v
a
t
i
o
n
s
h
o
u
l
d
b
e
l
e
s
s
t
h
a
n
5
m
Indoor unit
e
l
e
v
a
t
i
o
n
s
h
o
u
l
d
b
e
l
e
s
s
t
h
a
n
5
m
Curled tube for
returning water
Outdoor unit
3. REFRIGERANT PIPING
l The maximum length of the connecting refrigerant piping between indoor unit
and outdoor unit is 15m and the maximum elevation difference between indoor
and outdoor units are 5m.
l If the refrigerant piping is longer than 7m,additional refrigerant charge 20g/m for
below 1/2 inch gas pipe and 30g/m for below 5/8 or 3/4 inch gas pipe is advis-
able.
l Outside diameter of the refrigerant piping is as following.
Models
OD of liquid pipe
(small pipe)
OD of gas pipe
(large pipe)
7K, 9K (COOLING ONLY & HEAT PUMP 6mm or 1/4 inch 10mm or 3/8 inch
12K, 18K,24K ( COOLING ONLY &
HEAT PUMP)
6mm or 1/4 inch 12mm or 1/2 inch