Undesirable signal fluctuations can be suppressed through the adjustable filter in the
parameter td “Filter time constant” (see Fig. 6.1, Table 7.1).
The filter time constant can be set within the range 0…10 seconds. The higher the value, the
slower the display reaction to changes of the input signal and the lower the susceptibility to
interference. The filter is deactivated if td = 0.
Fig. 6.1
Square root function
This function is intended for transmitters with the square characteristic. To enable the
function, the parameter Sqrt must be set to ON.
Alarm
The alarm function compares the input signal with the setpoint limits and makes the display
blink with frequency about 2 Hz, depending on the parameter d.FnC (see Fig. 6.2, Table 7.1)
Fig 6.2 Alarm function
Alarm outside
limits
t
t
t
Alarm within
limits
SP.Hi
SP.Lo
T