7 Programming
Use the button to enter the programming mode or to apply the changes.
Use the buttons and to select or change the parameter. Press and hold the button to
activate the ramp function while changing parameter.
To return to the operating mode, the button must be pressed for longer than 5 s.
If no button is pressed within 20 s, the device reverts to operating mode automatically.
The parameter list is presented in Table 7.1 and the flowchart in Fig. 7.1.
Table 7.1
Name Display Parameter Valid value Description Default
PS
PS
Access protection
ON
OFF
OFF
di.P
di.P
Decimal point
----
0000
--.--
---.-
000.0
--.—
00.00
-.---
0.000
di.Lo
di.Lo
Lower measuring
limit
-999...9999
affected by di.P
4.00
di.Hi
di.Hi
Upper measuring
limit
-999...9999
affected by di.P
20.00
td
td
Filter time
constant
0…10 s 0
SQrt
SQrt
Square root
function
ON
OFF
OFF
d.FnC
d.FnC
Alarm function
oFF
OFF
OFF
U
Alarm outside
limits
П
Alarm within
limits
SP.Lo
SP.Lo
Lower setpoint
limit
-999...9999
affected by di.P
4.00
SP.Hi
SP.Hi
Upper setpoint
limit
-999...9999
affected by di.P
20.00