10.5  Alarm Settings (ID 551-950)
Global Parameters (ID: 551-600)
;551; ;Alarm on prog. relay (255 is NU); ;255; ; ;
x Replace 255 by the Alarm Code you wish for programming the relay user selectable 3
x See previous codes for the T2S and Enclosed list for the TSI.
;553;; ;MAJ relay temporization; ;60; ;sec;
x Temporization of Urgent alarm (from 0 to 65536 sec)
;554; ;MIN relay temporization; ;30; ;sec;
x High DC voltage – a higher value re-starts the DC/AC converter
;556; ;Saturation alarm threshold; ;100; ;%;
x Level of load that generates an alarm indicating there is a risk of overload.
x This parameter takes into account the redundancy defined previously
x I.e. P ex : system with 4 modules with 1 redundant –> 80 % of 3 modules
;558; ;AC
in
is present (1:true 0:false); ;1; ; ;
x Allow to inhibit the alarm when ACin not Present
x 1 –> gives alarm when main Network is not Present
x 0 –> no alarm when main Network is not Present (AC in not available or Regular inverter)
;570; ;Log near. full thresh. (100-200); ;180; ; ;
x Number of messages in the Logfile. It is from the Logfile that alarm is generated when the
Logfile is about completed.
Configuration of types of Al arms
- Alarm Type (ID : 601 - 900) : Minor(1) - Major(2) - No Alarm(0)
x Choice for type of alarms as detailed hereafter
x No Alarm = 0 / Minor = 1 / Major = 2
;828; ;227.DIG INP1 FAILURE; ;0; ; ;
x Type of alarms for Digital inlet 1 (Inlet to be configured by user)