Instruction Manual

99
Doc. #: 0260011-J0 Rev B
;829; ;228.DIG INP2 FAILURE; ;0; ; ;
x Type of alarms for Digital inlet 2 (Inlet to be configured by user)
;830; ;229.REDUNDANCY LOST; ;1; ; ;
x Activates when redundancy is lost
;831; ;230.REDUND + 1 LOST; ;2; ; ;
x Activates when more than # of modules of redundancy are lost
;832; ;231.SYS SATURATED; ;1; ; ;
x Type of alarms when the threshold of pre-alarm “overload” is exceeded
;833; ;232.MAIN SOURCE LOST; ;2; ; ;
x Type of alarm when Main source is lost
x In AIM2500 mode : Main source is ACin = Network
x In ON LINE mode : Main source is DCin = battery
;834; ;233.SEC SOURCE LOST; ;1; ; ;
x Activates when Secondary source is lost
x In AC/AC mode : Secondary Source is DCin = battery
x In ON LINE mode : Secondary Source is ACin = Network
;835; ;234.T2S BUS FAIL; ;2; ; ;
x Activates when the T2S is lost
;836; ;235.T2S FAILURE; ;2; ; ;
x Activates when the T2S is not running
;843; ;242.LOG NEARLY FULL; ;0; ; ;
x Activates when the logfile is nearly full