Instruction Manual

Doc. #: 0260011-J0 Rev B
30
3.8  AMPS24 HP - Recommended DC Breaker and Wire Sizes
The recommendations in this table are for reference only. A registered professional engi-
neer must review and approve or modify these recommendations in compliance with appli-
cable national and local electrical and building codes.
NOTE:
Maximum wire gauge size is 350 kcmil; 4/0 or smaller is recommended, 90°C or better copper only.
Model Recommended minimum DC Breaker
rating (100% rated per feed),
Maximum DC Input
Wattage
Maximum DC
Input Current @
48Vdc, full load
Single DC feed Dual DC feed
AMPS24-2-24 x 300 21.4 kW 480 A
AMPS24-2-21 x 250 18.7 kW 406 A
AMPS24-2-18 x 225 16 kW 333 A
AMPS24-2-9 250 125 8 kW 166 A
AMPS24-2-12 300 150 10.7 kW 240 A
AMPS24-3-18 x 225 16 kW 350 A
AMPS24-3-13.5 350 175 15 kW 250 A
AMPS24-1-10.5 250 125 9.4 kW 203 A
AMPS24-1-12 300 150 10.7 kW 240 A
AMPS24-1-9 250 125 8 kW 166 A
AMPS24-1-6 150 75 5.4 kW 120 A
AMPS24-1-4.5 120 60 4 kW 83 A
Torque specifications for DC wiring (3/8" bolts that attach the DC lugs at the back of the DC
distribution box) are as follows:
Imperial: 190 – 240 inch/lbs
Metric: 21.5 – 27.1 N-m