Instruction Manual

41
Doc. #: 0260011-J0 Rev B
GND GND
DC plus
Feed 2
DC minus
Feed 2
DC plus
Feed 1
DC minus
Feed 1
CAUTION!
Dual feed provides capacity sharing, but NO REDUNDANCY. The loss of one battery string
will result in the loss of half the inverters.
5.3.4  DC Bat tery Wiring with Independent Dual A/B Feed 
Figure 21 DC battery wiring with independent dual A/B feed
AMPS24 HP
AC
+
+
To
MGB