Instruction Manual

Doc. #: 0260011-J0 Rev B
48
21. Use the CXCU GUI as follows to verify that the modules are recognized and the voltages and
currents of the modules are displayed. (Ignore any alarms at this point. The current readings at
no load are not very precise.)
a. Select Inverters > View Live Status.
b. In the Inverter Report screen, locate the module for AC phase 1 by clicking each row until
the LEDs of the inverter, in the first phase 1 shelf, flash for a few seconds.
c. Using the pull down box in the Module Nu mber column, set the module number to 1 to
correspond to AC phase 1.
d. If this is a multiple phase system,locate the module for AC phase 2 by clicking each row in
the Inverter Rep ort screen until the LEDs of the inverter, in the first phase 2 shelf, flash for a
few seconds.
e. Use the pull down box to set the module number to 2 to correspond to AC phase 2 (for split
phase, 2-pole and 3 phase systems).
f. Repeat for a third module (select 3 to correspond to AC phase 3) if the system is 3 phase.
Figure 30 Inverters > View Live Status
e
a
step
b
step
c
step
d
step
step