6.2.6  Manage Config File
The inverter settings have their own configuration and are not part of the full site configuration file.
Refer to Chapter 10 for a list of the configuration file parameters and steps to save the file and upload
it to another system.
6.2.7  Alarms
Standard Inverter Alarms
Alarms for the following conditions can be configured from the Alarms > Configure Alarms menu
category (refer to the controller software manual for more details on alarm configuration):
Alarm Name Alarm Condition
Inverter Major Fail Count Number of failed Inverters equals or exceeds a user congured threshold
Inverter Minor Fail Count Number of failed Inverters equals or exceeds a user congurable
threshold
Inverter Comms Lost Controller loses communications with any one inverter. The number of
inverters must be correctly identied in the Inverters > Set Output menu.
Inverter AC Input Fail Main AC input of the inverter is lost
Inverter Alarm Any individual or system alarm is detected
Figure 43 Configure alarms window
Custom Inverter AlarmsMapping Alarms to Relays
Custom inverter alarms can be mapped through the digital inputs to available relays. Refer to the
latest version of the CXCU Controller software manual.