Instruction Manual

Doc. #: 0260011-J0 Rev B
68
7.  Preventive Maintenance
This equipment requires regular maintenance. Maintenance must be performed by qualified service
personnel only. Contact Alpha Technologies at 1-888-462-7487 for any assistance with maintenance.
WARNING!
WARNING: HIGH VOLTAGE AND SHOCK HAZARD Use extreme care when working in-
side the enclosure/shelf while the system is energized. Do not make contact with live com-
ponents or parts. Static electricity may damage circuit boards, including RAM chips. Always
wear a grounded wrist strap when handling or installing circuit boards. Ensure redundant
modules or batteries are used to eliminate the threat of service interruptions while perform-
ing maintenance on the system’s alarms and control settings.
7.1  Recommended maintenance schedule
Task: Interval
Clean ventilation openings 1-6 month
Inspect all cable connections, re-torque if necessary 1 year
Verify alarm/control settings 1 year
Verify alarm relay operation 1 year
Verify circuit breaker operation 1 year
Battery maintenance 3 months
7.2  Tools and Equipment
Table I Tools
Required Service /Maintenance Commissioning
Torque wrench X X
#2 Philips screw driver X X
#2 at head screw driver (3/16") width head X
#1 at head screw driver (1/8") width head X
Small at head screw driver (1/16") width head X X
9/16" hex driver X
3/8" hex driver X
7/16" combo wrench X
7/16" at gear ratchet X
9/16" combo wrench X
9/16" at gear ratchet X
11/16" combo wrench X
11/16" at gear ratchet X
6" ratchet extension X
3" ratchet extension X
3/8" ratchet socket X