Instruction Manual
83
Doc. #: 0260011-J0 Rev B
Table K — Inverter Alarm Codes
Alarm Type Description Cause Solution
229 REDUNDANCY
LOST
229 and text "Redundancy
Lost" when the condition is
true
Lost of inverter redundancy Replace defective inverter or
adapt conguration
230 REDUND + 1
LOST
Generate alarm code 230
and text "Redundancy + 1
Lost" when the condition is
true
Lost of inverter redundancy +
1 inverter
Replace defective inverter(s)
or adapt conguration
231 SYS
SATURATED
Generate alarm code 231
and text "Sys Saturated"
when the condition is true
Load of system greater than
the preset value
Reduce load or add inverter
on the system, or change the
alarm level trigger.
232 MAIN SOURCE
LOST
Generate alarm code 232
and text "Mains source lost"
when the condition is true
Priority source lost (depends
on the conguration AC/AC
or Online)
1) In AC/AC conguration:
Reconnect AC IN or check
conguration or check
live value. 2) In Online
conguration: Reconnect
DC or check conguration or
check level voltage
233 SEC SOURCE
LOST
Generate alarm code 233
and "Sec Source Lost"
when the condition is true
Secondary source
lost (depends on the
conguration AC/AC or
Online)
1) In ONLINE conguration:
Reconnect AC IN or check
conguration or check
live value. 2) In AC/AC
conguration: Reconnect
DC or check conguration or
check level voltage
234 T2S BUS FAIL Generate alarm code 234
and "T2S Bus Fail" when
the condition is true
The communication bus to
T2S has failed
Hardware problem. Replace
T2S
235 T2S FAILURE Generate alarm code 235
and text "T2S Failure" when
the condition is true
T2S has failed Hard ware problem. Replace
T2S
236 T2S STARTED Write event "T2S Started" in
log le when T2S is started
(powered up)
T2S has started
237 LOG CLEARED Write event "Log Cleared"
in log le when the log is
cleared
T2S has cleared the log
238 CONFIG
MODIFIED
Write event "Cong
Modied" in log le when
conguration is modied.
Conguration is modied
239 NEW MOD
DETECTED
Write event "New Mod
Detected" in log le when
new module is seen by T2S
One more module is plugged
240 DATE & TIME
MOD
Write event "Date & Time
Mod" in log le when date
and/or time are modied
Date and time are modied
241 CFG READ IN
MOD
Write event "Cfg Read In
Mod" in log le when T2S
had read the conguration
le from TSI inverter.
Tipically after insterting new
T2S on live system.
T2S has read the CFG
242 LOG NEARLY
FULL
Generate alarm code 242
and text "Log Nearly full"
when the condition is true
This item will be set as, No
alarm, Minor or major alarm.
(see conguration le)
Clear log le