Instruction Manual

87
Doc. #: 0260011-J0 Rev B
9.4  Specifications for AIM 1500 Module
General specications:
EMC (immunity) EN 61000-4
EMC (emission) EN55022 (Class A), FCC 47 VFR Part 15, class A
Safety IEC 60950, UL 1778 Issue 4
Cooling Forced Air
MTBF 240000 hrs
Efciency (typical)
AC Input Mode 93%
DC Input Mode 90%
AC Output Power
Nominal 1500 VA
Resistive Load 1200 W
Overload Capacity (short) 150% @ 5 sec
Overload Capacity (permanent) 110%
Nominal 48 V
Range (Vdc) 40 to 60 V
Nominal Current (@40 Vdc) 33 A
Max input current (5 s) 50 A
Voltage Ripple 2 mV
AC Input Specications
Nominal voltage (AC) 120 Vac
Voltage range (AC) 83 to 140 Vac
Power factor > 99%
Frequency range (selectable) 60 Hz
Frequency Tolerance ± 3 Hz (Adjustable)
AC Output
Nominal (AC)* 120 Vac Accuracy 2%
Frequency 60 Hz (Same as input frequency in AC/AC mode)
Frequency accuracy 0.03%
Transient load recovery time 0.4 ms
Transfer Performance
Maximum Voltage interruption 0 sec
Total Transient voltage duration 0 sec
Environmental
Operating Temperature: -20° to +50°C
Storage Temperature: -20 to +70°C
Humidity: Up to 95% non-condensing
Elevation: <1500M
Mechanical
Dimensions H x W x D mm (in): 90 x 101.6 x 317.5 (3.5 x 4 x 12.5)
Weight kg (lb): 2.4 (5.3)