Instruction Manual

91
Doc. #: 0260011-J0 Rev B
10.3  Global Settings (ID 1 – 50)
;1; ;Number of inverter modules in phase 1; ;4;
;2; ;Number of inverter modules in phase 2; ;4;
;3; ;Number of inverter modules in phase 3; ;4;
x Number of inverters present (Here shown as 4 modules) in each phase
x Range: 0 - 32, Default: 1
x min:0 1 32
x (same value for AC
in
and AC
out
)
;21; ;Amount of redundancy in phase 1; ;1;
;22; ;Amount of redundancy in phase 2; ;1;
;23; ;Amount of redundancy in phase 3; ;1;
x Number of redundant inverters in each phase (Here shown as 1 module)
x Range: 0 - 32, Default: 0
x When no inverter failed = no alarm
x When # of inverters failed redundancy (if different than 0) = Minor alarm (non urgent)
x When # of inverters failed > redundancy = Major alarm (urgent)
;40; ;Number of DC input groups; ;1;
x Number of DC input groups
x Range: 1 - 8, Default: 1
x Allows inverters groups to be supplied from sets of batteries that are physically separated
;41; ;Number of AC input groups; ;1;
x Number of AC input groups
x Range: 1 - 4, Default: 1