Instruction Manual

93
Doc. #: 0260011-J0 Rev B
;80; ;Short Circuit Voltage Threshold; ;80; ;V;
x Minimum Voltage Threshold where module considers that outlet is in short circuit
x Adjustable from 20 to 100 Vac, default: 80 Vac
;81; ;Short Circuit Hold Time; ;60.0; ; sec;
x Time Duration when the module tries to eliminate the short-circuit existing on the outlet
x When this time expires and the voltage is less than the value on line 80, the module stops.
x Adjustable from 0.1 to 600 sec, default: 60 sec
;82; ;Booster 10 x I
in
(0 : OFF, 1 : ON) ; ;1; ; ;
x Turns off the Booster option which generates a current of 10 x I
in
for 20ms in case of short-
circuit.
;90; ;Max current (as percentage of nominal current); ;110; ;%;
x Maximum Current that module can supply.
x Adjustable from 100 to 110 % for AIM2500
;91; ;Max power (as percentage of of nominal power) ; ;110; ;%;
x Maximum Power that the module can supply.
x ALWAYS RECORD THE SAME VALUES for 90 and 91
;92; ;Max Overload Duration); ;15; ;sec;
x Maximum Time Duration when module can run with overload.
x Adjustable from 0 to 15 sec, default: 15 sec
;100; ;Synchronization Tracking Speed; ;0; ; ;
x Speed with which the module tries to synchronize AC
out
x Possible values:
Speed Value Frequency (Hz/sec)
very fast -2 2.5
fast -1 1.25
normal (default) 0 0.5
slow 1 0.25
very slow 2 0.1