Instruction Manual

Doc. #: 0260011-J0 Rev B
94
;101; ;Remote OFF disable ACin Power; ;0; ; ;
x 0 –> Normal mode, default
x 1 –> ACin power is de-activated
;102; ;Negative Power (0 : OFF, 1 : ON); ;1; ; ;
x 1 –> ON, default
;103; ;External clock (0 : OFF, 1 : ON); ;0; ; ;
x 0 no in service protection
x 1 in service protection
;160; ;OUT 1 : phase shift (-180 to 360, default 0); ;0; ;deg;
;161; ;OUT 1 : Nominal Output Voltage (100 to 140); ;120; ;V;
x Record of the phase shift and nominal Outlet voltage.
x Phase shift range: -180 to 360, default: 0 deg
x Nominal output voltage range: 100 to 140, default: 120 V
;170; ;OUT 2 : phase shift; ;120; ;deg;
;171; ;OUT 2 : Nominal Output Voltage; ;120; ;V;
x Record the phase shift and the nominal Outlet voltage.
x Range and defaults same as OUT 1
;180; ;OUT 3 : phase shift; ;240; ;deg;
;181; ;OUT 3 : Nominal Output Voltage; ;120; ;V;
x Record the phase shift and the nominal Outlet voltage.
x Range and defaults same as OUT 1
Parameters for DC Groups
;260; ;DC 1 : Vdc_in Low Start; ;49; ;V;
x Low DC Voltage – a higher value causes the converter DC/AC to re-start
x Range: 39 to 61, default: 49 V